Cisco 3750X / 38xx stack reports incorrect power supply status

Cisco 3750X / 38xx stack reports incorrect power supply status. You may find that your Cisco 3750X / 38xxstacked switches report a faulty/not functioning power supply via the Hardware Health Sensors in NPM. All NPM environments. This is caused by the device reporting a value of 6 for the affected power supply and can be seen in the SNMP walk results from the device using the instructions below. According to the below article, this is fixed in Cisco IOS versions 15.0(2)SE3,12.2(55)SE8, 16.12.04

First published date

10/19/2018 6:29 PM

Last published date

12/23/2025 12:30 AM

Overview

You may find that your Cisco 3750X / 38xx stacked switches report a faulty/not functioning power supply via the Hardware Health Sensors in NPM.

 

This is illustrated in the following screenshot:

 

Product section

Network Performance Monitor

Cause

This is caused by the device reporting a value of 6 for the affected power supply and can be seen in the SNMP walk results from the device using the instructions below:

 

SolarWinds SNMP Walk: A new tool for collecting SNMP MIB walks

Public article: https://support.solarwinds.com/SuccessCenter/s/article/Troubleshoot-connectivity-and-MIB-issues-with-SolarWinds-SNMP-walk-IPv4-only?language=en_US

Search for .1.3.6.1.4.1.9.9.13.1.5.1.3 and .1.3.6.1.4.1.9.9.13.1.5.1.4 in the results.

Specifically, the OID strings will appear as such (note that the UID 1058 and 1061 may differ in your environment):

.1.3.6.1.4.1.9.9.13.1.5.1.3.1058 = INTEGER: 6
.1.3.6.1.4.1.9.9.13.1.5.1.3.1061 = INTEGER: 1
.1.3.6.1.4.1.9.9.13.1.5.1.4.1058 = INTEGER: 2
.1.3.6.1.4.1.9.9.13.1.5.1.4.1061 = INTEGER: 2

Values:

  1. normal(1): the environment is good, such as low temperature.
  2. warning(2): the environment is bad, such as temperature above normal operation range but not too high.
  3. critical(3): the environment is very bad, such as temperature much higher than the normal operating limit.
  4. shutdown(4): the environment is the worst, the system should be shut down immediately. 
  5. notPresent(5): the environmental monitor is not present, such as temperature sensors do not exist.
  6. notFunctioning(6): the environmental monitor does not function properly, such as a temperature sensor generates abnormal data like 1000 C.


 

Resolution

  1. According to the following article, this is fixed in Cisco IOS versions 15.0(2)SE3 & 12.2(55)SE8: https://supportforums.cisco.com/discussion/12135611/3750-management-server-show-rps-notexist-statenotfunctioning 
  2. If this update is not available to you or if you are unable to upgrade the IOS on your Cisco 3750X, please note that there is a Feature Request to address this issue from the SolarWinds side as a work-around. However, we can't guarantee this will be fulfilled as the root cause is improper SNMP results from the Cisco 3750X.  https://thwack.solarwinds.com/ideas/2182